900-1:
SPRAY ASSEMBLY
 |
The
water spray system is comprised of the Mounting Flange,
Gasket, Close Nipple, Strainer, Nozzle and Solenoid
Valve. The Solenoid Valve portion of the assembly partly
relies upon differential water pressure across a diaphragm
to open and close the valve. This flow of water takes
place in small diameter orifices which should be kept
free from debris as much as possible. Therefore, the
Nozzle and Spray Assembly includes a strainer immediately
upstream of the valve assembly. The minimum water pressure
is 50 PSI and the maximum recommended water pressure
is 100 PSI - achievement of which may require a pressure
reducer.
|